testo 330-2 LL Facelift

  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
  • testo 330-2 LL Facelift
TESTO AG
testo 330-2 LL flue gas analyzer with long-life gas sensors; incl. O2-/CO-sensor; without H2-compensation, rech. battery
 
Part #: 0632 3307

Description

Thanks to the new instrument functions, the Testo flue gas analyzers of the new testo 330-LL series now offer you even more professional and reliable support. These are the main features:
 
• High-resolution colour display for the graphic representation of your measurement data
• Extended measurement menus – such as gas pipe testing – for a comprehensive analysis of your heating system
• Logger function for easy long-term recording of the measurement curve
• Graphic processing of measurement data
 •Measurement data management: it is possible to export the measurement protocols in Excel optionally via mini-USB. Further options for managing the measurement data are offered by the PC software easyheat (optional) and the free app TestoDroid for android smartphones and tablets
• Instrument diagnosis function uses easy „traffic light’’ presentation to enable comprehensive instrument diagnosis
• Pressure measurement up to 300 mbar
• User-defined fuels
• TÜV-tested according to 1. BImSchV / EN 50379 Part 2 for O2, °C, hPa and CO with H2-compensation
• Powerful memory management: 500,000 readings
• IrDa/ Bluetooth interface for data transfer to Pocket-PC / laptop / printer
• USB interface for data readout to a PC software
• ZIV (Central Guild Association) driver for all standard industry software packages
• In CO measurement, from 8.000 ppm, automatic dilution is carried out up to min. 30,000 ppm CO
• Integrated gas and draught zeroing without probe removal: The probe can remain in the flue during zeroing

Options:
• Option: Fine draught measurement, Resolution 0.1 Pa, measurement range to 100 Pa (instead of the standard draught measurement)
• Option fine differential pressure measurement
• Option: NO sensor, meas. range 0 to 3000 ppm, 1 ppm resolution
• Option H2-compensated CO cell
• Option COlow sensor
• Option Bluetooth
 

testo 330LL - Flue Gas Analyser

  • Cable, 1.5 m long

    # 0430 0143

    Сonnects  CO2 probe with plug-in head to meas. instrument (PUR coating material)

  • Hose extension, 2.8 m

    # 0554 1202

    Еxtension cable for probe and analyser

  • 6 mm, probe stop

    # 0554 3329

    Steel, with spring clamp and handle, Tmax 500 °C

  • Multi-hole probe shaft

    # 0554 5762

    300 mm long, Ø 8 mm, for mean CO calculation

  • Probe shaft, 335 mm long

    # 0554 8764

    With probe stop, ∅ 8 mm, Tmax 1000 °C

  • Probe shaft, 700 mm long

    # 0554 8765

    With probe stop, ∅ 8 mm, Tmax 1000 °C

  • Probe shaft, 180 mm long

    # 0554 9760

    ∅ 8 mm, Tmax 500 °C

  • Probe shaft, 300 mm long

    # 0554 9761

    ∅ 8 mm, Tmax 500 °C

  • Probe shaft, 300 mm long

    # 0554 9763

    ∅ 6 mm, Tmax 500 °C

  • Flexible probe shaft

    # 0554 9764

    330 mm long, Ø 10 mm, Tmax 180 °C

  • Mini ambient air probe

    # 0600 3692

    Tmax +80°C, for separate ambient air temperature measurement Meas. Range 0 to +80 °C

  • Pipe wrap probe Type K (NiCr-Ni)

    # 0600 4593

    For pipes with diameter of up to 2", for flow/return temp. meas. in hydronic systems Meas. Range -60 to +130 °C

  • Flue gas probe

    # 0600 9760

    180 mm long, ∅ 8 mm, Tmax 500 °C, TÜV approval

  • Flue gas probe

    # 0600 9761

    300 mm long, ∅ 8 mm, Tmax 500 °C, TÜV approval

  • Flue gas probe

    # 0600 9762

    180 mm long, ∅ 6 mm, Tmax 500 °C

  • Flue gas probe

    # 0600 9763

    300 mm long, ∅ 6 mm, Tmax 500 °C

  • Flexible flue gas probe

    # 0600 9770

    Тhermocouple NiCr-Ni; hose 2.2. m; dirt filter; length 330 mm; dia 9 mm; Tmax. 180 °C; short-term 200 °C; bending radius max. 90° for measuring at inaccessible points.

  • Combustion air temperature probe

    # 0600 9787

    Immersion depth 190 mm Meas. Range 0 to +100 °C

  • Combustion air temperature probe

    # 0600 9797

    Immersion depth 60 mm Meas. Range 0 to +100 °C

  • Quick-action surface probe with sprung thermocouple strip Type K (NiCr-Ni)

    # 0604 0194

    Мeasuring range short-term to +500°C (Plug-in head, connection cable 0430 0143 or 0430 0145 required) Meas. Range -200 to +300 °C

  • Dual wall clearance probe

    # 0632 1260

    For O2 supply air measurement

  • Gas leak probe

    # 0632 3330

    Meas. Range 0 to +10000 ppm CH4 / ppm C3H8

  • Ambient CO probe

    # 0632 3331

    (for detecting CO in buildings and rooms) Meas. Range 0 to +500 ppm CO

  • Fine pressure probe

    # 0638 0330
    Fine pressure probe - for heating system checks / 4 pascal measurement
     
    Temperature - Type K TC
    Measuring range                  
    Depends on probe, max. -40 to +1200 °C
     -200 to +300 °C (with surface probe 0604 0994 (accessory))
    Accuracy
    ±0.5 °C (-40 to +100 °C)
    ±0.5 % of mv (Remaining Range) additionally ±1 digit, additionally accuracy of probe
    Resolution
     0.1 °C
     
    Differential Pressure          
                                                                                                                                         
    Measuring range
    --9999.9 to +9999.9 Pa
    Accuracy
    ±0.3 Pa (0 to +9.99 Pa)
    ±3 % of mv (+10.00 to +9999.9 Pa) additionally ±1 digit
    Resolution
    0.01 Pa (-149.99 to +149.99 Pa)
    0.1 Pa (Remaining Range)
     
    Velocity / Volume flow
    Measuring range                  
     0.15 to 3 m/s                                                                                                               
    Resolution
    0.1 m/s
     

  • O2 sensor for testo 330-1 LL/-2 LL

    # 0393 0002
  • CO sensor (without H2-compensation)

    # 0393 0051

    (for testo 330-1 LL/-2 LL)

  • CO sensor (H2-compensated)

    # 0393 0101

    (for testo 330-1 LL/-2 LL)

  • COlow sensor 0 to 300 ppm

    # 0393 0103

    (for testo 330-1 LL/-2 LL)

  • USB connection cable, instrument to PC

    # 0449 0047
  • Spare battery 2600 mA

    # 0515 0107
  • Versatile system case

    Versatile system case

    # 0516 0331
    Without sections, attachable to basic system case (For easy storage of analyser and additional accessories)
  • System case

    # 0516 3300

    (height: 130 mm) for instrument, probes and accessories

  • Basic system case

    # 0516 3331

    With two levels for analyser, probes and additional accessories

  • Adhesive pockets (50 off)

    # 0554 0116

    For printout, paper barcode labels

  • Smoke tester with oil

    # 0554 0307

    Soot sheet, for measuring soot in flue gas

  • Barcode labels, self-adhesive (1200 off)

    Barcode labels, self-adhesive (1200 off)

    # 0554 0411
    (for labelling site with barcode, printing via software)
  • Testo fast printer

    # 0554 0549

    With wireless infrared interface, 1 roll thermal paper and 4 AA batteries (for printing out measurements on site)

  • BLUETOOTH® printer

    # 0554 0553

    Set with wireless Bluetooth interface, incl. 1 roll thermal paper, rechargeable battery and mains unit

  • Spare thermal paper for printer (6 rolls

    # 0554 0568

    (measurement data documentation legible for up to 10 years)

  • 100-240 V DC mains unit

    # 0554 1096

    (for testo Saveris base, router, converter, Ethernet probe)

  • Charger for spare battery

    # 0554 1103
  • Hose connection set

    # 0554 1203

    For separate gas pressure measurement

  • Differential temperature set

    Differential temperature set

    # 0554 1204
    Сonsisting of 2 pipe clamp probes and adapter
  • Instrument cleaner (100 ml)

    Instrument cleaner (100 ml)

    # 0554 1207
    (for hassle-free and fast removal of dirt from housing, display screen, keypad, probe handle and probe cable)
  • Full version EasyHeat + EasyHeat Mobile (for PC und PDA)

    # 0554 1210
  • Update: easyheat.mobile

    Update: easyheat.mobile

    # 0554 1211
    Software for Pocket PC for mobile applications. (Only for customers who already have easyheat PC software in use.)
  • Pressure set for testing gas line

    # 0554 1213
  • Retrofit COlow sensor

    Retrofit COlow sensor

    # 0554 2103
    (Measuring range 0 -to 300 ppm, resolution 0.1 hPa)
  • Retrofit NO sensor, measuring range 0 to 3000 ppm, resolution 1 ppm

    # 0554 2151

    (for testo 330-1 LL/-2 LL)

  • easyheat PC analysis software

    # 0554 3332

    Shows measurement in form of diagrams, tables and manages customer data

  • Spare particle filter (10 off)

    # 0554 3385
  • Retrofit: NOlow sensor

    # 0554 3931

    (meas. range 0 to 300 ppm, 0.1 ppm resolution)

  • NO sensor 0 to 3000 ppm

    # 3306_no_cell

    (for testo 330-1 LL/-2 LL)

  • ISO calibration certificate/flue gas

    ISO calibration certificate/flue gas

    # 0520 0003
    (calibration points 2.5% O2; 100 and 1000 ppm CO; 800 ppm NO; 80 ppm NO2; 1000 ppm SO2)

 

Flue gas O₂                                        
                                     
Measuring range
0 to 21 Vol.%
Accuracy
±0.2 Vol.%
Resolution
0.1 Vol.%
Reaction time t₉₀                                         
< 20 s                                                             
 
Flue gas CO (with H₂-compensation)
                                                                      
Measuring range
0 to 8000 ppm
Accuracy
±10 ppm or ±10 % of mv (0 to 200 ppm)
±20 ppm or ±5 % of mv (201 to 2000 ppm)
±10 % of mv (2001 to 8000 ppm)
Resolution
1 ppm
Reaction time t₉₀
< 60 s
 
Flue gas COlow                                  
                                                                      
Measuring range
0 to 500 ppm
Accuracy
±2 ppm (0 to 39.9 ppm)
±5 % of mv (40 to 500 ppm)
Resolution
0.1 ppm
Reaction time t₉₀
< 40 s
 
CO determination (with
H₂-compensation), automatic dilution
                                                                   
Measuring range
0 to 30000 ppm
Accuracy
±100 ppm (0 to 1000 ppm)
±10 % of mv (1001 to 30000 ppm)
Resolution
1 ppm
 
Flue gas NO                                         
                                                                    
Measuring range
0 to 3000 ppm
Accuracy
±5 ppm (0 to 100 ppm)
±5 % of mv (101 to 2000 ppm)
±10 % of mv (2001 to 3000 ppm)
Resolution
1 ppm
Reaction time t₉₀
< 30 s
 
Flue gas Nolow                                   
                                                                     
Measuring range
0 to 300 ppm
Accuracy
±2 ppm (0 to 39.9 ppm)
±5 % of mv (40 to 300 ppm)
Resolution
0.1 ppm
Reaction time t₉₀
< 30 s
 
Flue gas Draught                               
 
Measuring range
-9.99 to +40 hPa
Accuracy
±0.02 hPa or ±5 % of mv (-0.50 to +0.60 hPa)
±0.03 hPa (+0.61 to +3.00 hPa)
±1.5 % of mv (+3.01 to +40.00 hPa)
Resolution
0.01 hPa
 
Temperature                                            
                                                                          
Measuring range
-40 to +1200 °C
Accuracy
±0.5 °C (0 to +100.0 °C)
±0.5 % of mv (Remaining Range)
Resolution
0.1 °C (-40 to +999.9 °C)
1 °C (> +1000 °C)
 
Flue gas degree of effectivity,      
Eta (calculated)                                           
                                                                          
Measuring range
0 to 120 %
Resolution
0.1 %
 
Flue gas loss (calculated)                
                                                                         
Measuring range
0 to 99.9 %
Resolution
0.1 %
 
Flue gas CO₂ calculation                 
(calculated from O₂)
                                                                         
Measuring range
0 to CO₂ max (Display range)
Accuracy
±0.2 Vol.%
Resolution
0.1 Vol.%
Reaction time t₉₀
< 40 s
 
Velocity / Volume flow                          
                                                                        
Measuring range
0.15 to 3 m/s
Resolution
0.1 m/s
 
Pressure measurement                     
                                                                       
Measuring range
0 to +300 hPa
Accuracy
±0.5 hPa (0.0 to 50.0 hPa)
±1 % of mv (50.1 to 100.0 hPa)
±1.5 % of mv (Remaining Range)
Resolution
0.1 hPa
 
Ambient CO                                               
       with CO probe                                   
Measuring range
0 to 500 ppm
Accuracy
±5 ppm (0 to 100 ppm)
±5 % of mv (> 100 ppm)
Resolution
1 ppm
Reaction time
Approx. 35 s
Ambient CO₂                                
with ambient CO₂probe                           
Measuring range
0 to 1 Vol.%
0 to 10000 ppm
Accuracy
±50 ppm or ±2 % of mv (0 to 5000 ppm)
±100 ppm or ±3 % of mv (5001 to 10000 ppm)
Reaction time
Approx. 35 s
Gas leak measurement for          
combustible gases
with gas leak detection probe   
Measuring range
0 to 10000 ppm CH₄ / C₃H₈; Display range
Accuracy
Signal optical display (LED) audible signal via buzzer
Reaction time t₉₀
< 2 s
Temperature                                
via the fine pressure probe                            
Measuring range
-40 to +1200 °C max. (dependent on probe)
Accuracy
±0.5 °C (-40 to 100 °C)
±0.5 % of mv (Remaining Range) plus probe accuracy
Resolution
0.1 °C
 
Memory                                                   
 
500.000 readings                                                          
Display
Colour graphic display with 240 x 320 Pixel
Storage temperature
-20 to +50 °C
Operating temperature        
-5 to +45 °C
Weight
600 g
Dimensions
270 x 90 x 65 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
Flue gas CO (with H₂-compensation)  

Measuring range

0 to 8000 ppm

Accuracy

±10 ppm or ±10 % of mv (0 to 200 ppm)
±20 ppm or ±5 % of mv (201 to 2000 ppm)
±10 % of mv (2001 to 8000 ppm)

Resolution

1 ppm

Reaction time t₉₀

< 60 s

 
Flue gas COlow                                                                                             

Measuring range

0 to 500 ppm

Accuracy

±2 ppm (0 to 39.9 ppm)
±5 % of mv (40 to 500 ppm)

Resolution

0.1 ppm

Reaction time t₉₀

< 40 s

 

CO determination (with

H₂-compensation), automatic dilution

                                                        

Measuring range

0 to 30000 ppm

Accuracy

±100 ppm (0 to 1000 ppm)
±10 % of mv (1001 to 30000 ppm)

Resolution

1 ppm

 
Flue gas NO                                                                                                  

Measuring range

0 to 3000 ppm

Accuracy

±5 ppm (0 to 100 ppm)
±5 % of mv (101 to 2000 ppm)
±10 % of mv (2001 to 3000 ppm)

Resolution

1 ppm

Reaction time t₉₀

< 30 s

 
Flue gas Nolow                                                                                            

Measuring range

0 to 300 ppm

Accuracy

±2 ppm (0 to 39.9 ppm)
±5 % of mv (40 to 300 ppm)

Resolution

0.1 ppm

Reaction time t₉₀

< 30 s

 
Flue gas Draught                             

Measuring range

-9.99 to +40 hPa

Accuracy

±0.02 hPa or ±5 % of mv (-0.50 to +0.60 hPa)
±0.03 hPa (+0.61 to +3.00 hPa)
±1.5 % of mv (+3.01 to +40.00 hPa)

Resolution

0.01 hPa

 
Temperature                                                                                                

Measuring range

-40 to +1200 °C

Accuracy

±0.5 °C (0 to +100.0 °C)
±0.5 % of mv (Remaining Range)

Resolution

0.1 °C (-40 to +999.9 °C)
1 °C (> +1000 °C)

 

Flue gas degree of effectivity,      

Eta (calculated)

                                                             

Measuring range

0 to 120 %

Resolution

0.1 %

 
Flue gas loss (calculated)                                                                           

Measuring range

0 to 99.9 %

Resolution

0.1 %

 

Flue gas CO₂ calculation             

(calculated from O₂)

                                                              

Measuring range

0 to CO₂ max (Display range)

Accuracy

±0.2 Vol.%

Resolution

0.1 Vol.%

Reaction time t₉₀

< 40 s

 
Velocity / Volume flow                                                                               

Measuring range

0.15 to 3 m/s

Resolution

0.1 m/s

 
Pressure measurement                                                                             

Measuring range

0 to +300 hPa

Accuracy

±0.5 hPa (0.0 to 50.0 hPa)
±1 % of mv (50.1 to 100.0 hPa)
±1.5 % of mv (Remaining Range)

Resolution

0.1 hPa

 
Ambient CO                                          with CO probe                                                     

Measuring range

0 to 500 ppm

Accuracy

±5 ppm (0 to 100 ppm)
±5 % of mv (> 100 ppm)

Resolution

1 ppm

Reaction time

Approx. 35 s

Ambient CO₂                                 with ambient CO₂probe                                             

Measuring range

0 to 1 Vol.%
0 to 10000 ppm

Accuracy

±50 ppm or ±2 % of mv (0 to 5000 ppm)
±100 ppm or ±3 % of mv (5001 to 10000 ppm)

Reaction time

Approx. 35 s

Gas leak measurement for          

combustible gases

with gas leak detection probe                                  

Measuring range

0 to 10000 ppm CH₄ / C₃H₈; Display range

Accuracy

Signal optical display (LED) audible signal via buzzer

Reaction time t₉₀

< 2 s

Temperature                                 via the fine pressure probe                                       

Measuring range

-40 to +1200 °C max. (dependent on probe)

Accuracy

±0.5 °C (-40 to 100 °C)
±0.5 % of mv (Remaining Range) plus probe accuracy

Resolution

0.1 °C

 
Memory                                                   
 
500.000 readings
Display
Colour graphic display with 240 x 320 Pixel
Storage temperature
-20 to +50 °C
Operating temperature        
-5 to +45 °C
Weight
600 g
Dimensions
270 x 90 x 65 mm
 

Enquiry Form

Related products

  • testo 320

    testo 320

    testo 320 flue gas analyzer with graphic display; incl. O2 cell; rech. battery and manual
  • testo 330-1 LL Facelift

    testo 330-1 LL Facelift

    testo 330-1 LL flue gas analyzer with long life gas sensors, incl. O2-/CO-sensor; without H2-compensation, rech. battery
  • Тesto 330i - flue gas analyzer

    Тesto 330i - flue gas analyzer

    New generation gas analyzers, the readings on your smartphone or tablet, very healthy - for harsh conditions